<?xml version="1.0" encoding="utf-8"?>
<!DOCTYPE article PUBLIC "-//NLM//DTD JATS (Z39.96) Journal Publishing DTD v1.3 20210610//EN" "https://jats.nlm.nih.gov/publishing/1.3/JATS-journalpublishing1-3.dtd">
<article article-type="research-article" dtd-version="1.3" xml:lang="en">
  <front xmlns:xlink="http://www.w3.org/1999/xlink">
    <journal-meta>
      <journal-id journal-id-type="elibrary">75504</journal-id>
      <journal-title-group>
        <journal-title>Magazine of Civil Engineering</journal-title>
        <trans-title-group xml:lang="ru">
          <trans-title>Magazine of Civil Engineering</trans-title>
        </trans-title-group>
      </journal-title-group>
      <issn pub-type="epub">2712-8172</issn>
    </journal-meta>
    <article-meta xmlns:xlink="http://www.w3.org/1999/xlink">
      <article-id pub-id-type="publisher-id">8</article-id>
      <article-id pub-id-type="doi">10.18720/MCE.84.8</article-id>
      <title-group>
        <article-title>Fireproof suspended ceilings with high fire resistance limits</article-title>
        <trans-title-group xml:lang="ru">
          <trans-title>Огнезащитные подвесные потолки с высокими пределами огнестойкости</trans-title>
        </trans-title-group>
      </title-group>
      <contrib-group>
        <contrib contrib-type="author">
          <contrib-id contrib-id-type="scopus">56826013600</contrib-id>
          <name>
            <surname>Gravit</surname>
            <given-names>Marina</given-names>
          </name>
          <xref ref-type="aff" rid="aff1"/>
          <email>marina.gravit@mail.ru</email>
        </contrib>
        <contrib contrib-type="author">
          <name>
            <surname>Golub</surname>
            <given-names>Elena</given-names>
          </name>
          <xref ref-type="aff" rid="aff2"/>
          <email>alen-go@bk.ru</email>
        </contrib>
        <contrib contrib-type="author">
          <name>
            <surname>Grigoriev</surname>
            <given-names>Denis</given-names>
          </name>
          <xref ref-type="aff" rid="aff3"/>
          <email>gdm@pptech.ru</email>
        </contrib>
        <contrib contrib-type="author">
          <name>
            <surname>Ivanov</surname>
            <given-names>Igor</given-names>
          </name>
          <xref ref-type="aff" rid="aff3"/>
          <email>info@pptech.ru</email>
        </contrib>
      </contrib-group>
      <aff id="aff1">Peter the Great St. Petersburg Polytechnic University</aff>
      <aff id="aff2">Peter the Great Saint Petersburg Polytechnic University</aff>
      <aff id="aff3">LLC «Fire Safety Technology»</aff>
      <pub-date publication-format="electronic" date-type="pub" iso-8601-date="2018-12-24">
        <day>24</day>
        <month>12</month>
        <year>2018</year>
      </pub-date>
      <issue>8</issue>
      <issue-id pub-id-type="publisher-id">84</issue-id>
      <fpage>75</fpage>
      <lpage>85</lpage>
      <self-uri xmlns:xlink="http://www.w3.org/1999/xlink" content-type="pdf" xlink:href="https://engstroy.spbstu.ru/userfiles/files/2018/8(84)/08.pdf"/>
      <abstract xml:lang="en">
        <p>Suspended ceiling is an effective way to fire protection of horizontal structures with steel beams due to its lightness, reliability and functionality. Three designs of fireproof suspended ceiling with silicate plates on cement binder are considered. A detailed description of the tested structures is given. Experiments were carried out to determine the fire resistance of the samples. The results of fire tests on suspended ceilings under standard fire temperature regime are presented in this study. It was found that the structures that have shown their effectiveness under the standard regime cannot satisfy the conditions of the hydrocarbon temperature regime. For the purpose of efficiency in the hydrocarbon regime and isolating the beams from the fire, in addition to fire-retardant plates, non-combustible heat insulation was used in the construction of the ceiling. The results of testing the ceiling with fire-retardant plates and rock wool when creating a hydrocarbon fire regime are given. It is shown that at the end of the fire exposure, the limiting state of the loss of bearing capacity and the loss of integrity was not fixed, visible changes during the test period was not found.</p>
      </abstract>
      <kwd-group xml:lang="en">
        <kwd>oil and gas complex</kwd>
        <kwd>building structure</kwd>
        <kwd>steel construction</kwd>
        <kwd>fire resistance</kwd>
        <kwd>hydrocarbon fire</kwd>
        <kwd>standard fire</kwd>
        <kwd>suspended ceiling</kwd>
      </kwd-group>
    </article-meta>